Test sequence & procedure

The order tests are carried out in, and why that order matters — dead tests before energising, live tests after.

Dead tests, in order

Before energising: continuity of protective conductors (643.2), insulation resistance (643.3), protection by SELV/PELV/separation where relevant (643.4), and polarity (643.6).

  1. 1 Continuity of protective conductors (643.2)
  2. 2 Insulation resistance (643.3)
  3. 3 Protection by SELV, PELV or electrical separation where relevant (643.4)
  4. 4 Polarity (643.6)

BS 7671 Reg 643.1

Live tests, in order

After the dead tests and safe energising: earth fault loop impedance (643.7), prospective fault current (643.7.3.201), RCD operation (643.8), phase sequence for polyphase circuits (643.9), and functional testing (643.10).

  1. 1 Earth fault loop impedance (643.7)
  2. 2 Prospective fault current (643.7.3.201)
  3. 3 RCD operation (643.8)
  4. 4 Phase sequence for polyphase circuits (643.9)
  5. 5 Functional testing (643.10)

BS 7671 Reg 643.1

Test instrument accuracy and requirements

A basic measurement accuracy of 5 % is usually adequate; for analogue instruments, 2 % of full-scale deflection gives the required accuracy over a useful proportion of the scale. Operating accuracy in the field is always worse than basic accuracy — the BS EN IEC 61557 series requires a maximum operating error of no more than ±30 % of reading over the stated measurement range, taking worst-case environmental, supply and battery conditions into account. A low-resistance ohmmeter should derive its test current from a source with a no-load voltage between 4 V and 24 V and a short-circuit current of not less than 200 mA, and should cover 0.2 Ω to 2 Ω with a resolution of at least 0.01 Ω on digital instruments.

InstrumentStandardRequirement
Any test instrumentBS EN IEC 61557Maximum operating error ±30 % of reading over the stated measurement range
Low-resistance ohmmeterBS EN IEC 61557-4No-load voltage 4–24 V; short-circuit current not less than 200 mA; range 0.2–2 Ω; resolution at least 0.01 Ω (digital)
Insulation resistance testerBS EN 61557-2Capable of developing the required test voltage across the load

IET GN3 10th Ed §4.2–4.4 (pp.134–136)