Test & limiting values

The numbers the 2391-52 expects you to apply correctly: insulation resistance, earth fault loop impedance, disconnection times and RCD operating times.

Table 64 insulation resistance

SELV & PELV — 250 V DC test, minimum 0.5 MΩ. Up to and including 500 V (e.g. most LV circuits) — 500 V DC test, minimum 1.0 MΩ. Above 500 V — 1000 V DC test, minimum 1.0 MΩ.

Circuit nominal voltageTest voltage (DC)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V500 V1.0 MΩ
Above 500 V1000 V1.0 MΩ

BS 7671 Table 64 / Reg 643.3.2

Maximum earth fault loop impedance (Zs)

Maximum Zs depends on the protective device's type, rating and disconnection time — see the Max Zs calculator for the full Table 41.3 figures (0.4 s, 230 V) rather than memorising a single number here.

BS 7671 Table 41.3

Disconnection times (Table 41.1, U₀ 230 V)

TN system — 0.4 s for final circuits up to 63 A, 5 s for distribution circuits and final circuits over 63 A. TT system — 0.2 s for final circuits up to 63 A, 1 s for distribution circuits and final circuits over 63 A.

SystemFinal circuits up to 63 ADistribution circuits and final circuits over 63 A
TN0.4 s5 s
TT0.2 s1 s

BS 7671 Reg 411.3.2.2/.3, Table 41.1

RCD operating times

30 mA RCDs are used for additional protection. A general (non-delay) type must operate within 300 ms at its rated residual operating current IΔn; an S-type (time-delayed) device operates between 130 ms and 500 ms at IΔn.

Device typeOperating time at IΔn
General (non-delay)Within 300 ms
S-type (time-delayed)Between 130 ms and 500 ms

BS 7671 Reg 415.1.1 / 643.8

RCD test currents and expected times

GN3's recommended test set applies the residual current twice. At ½ × IΔn the RCD should not trip. At 1 × IΔn the maximum expected tripping time is 300 ms for a non-delay RCD to a harmonized standard, 500 ms for an S-delay type, and 200 ms for a non-delay RCD to BS 4293 or BS 7288:1990. BS 7671 does not require testing of RCDs at 5 × IΔn — the 40 ms figure at 5 × IΔn appears only among GN3's optional fault-finding tests, which are product-standard performance requirements rather than BS 7671 requirements.

Applied residual currentHarmonized, non-delayHarmonized, S-delayBS 4293 / BS 7288:1990, non-delay
½ × IΔnShould not tripShould not tripShould not trip
1 × IΔn300 ms500 ms200 ms

IET GN3 10th Ed Table 2.18 (p.96) / §2.6.18 (p.97)